Description
The CTI GG-2 is a two-channel gas detection controller with 4-20 mA inputs, built as a stand-alone safety system for engine rooms and other two-sensor applications. It interfaces with, but operates independently of, plant control systems.
Key specifications
- Inputs: two industry-standard linear 4-20 mA channels; configurable for CTI and other 4-20 mA gas sensors (not temperature monitoring)
- Relays: six total; (1) common horn, (1) common fault, (2) individual warn, (2) individual alarm; onboard buzzer works with the horn relay
- Analog outputs standard, for a plant PLC or other 4-20 mA panel
- Display: backlit graphic LCD with real-time status; menu-driven programming; default setpoints loaded
- Alarm log stores 10,000 events; calibration mode, relay test, latch/non-latch relays, downscale alarm for O2 monitoring, front-panel horn silence
- Power: 120 VAC at 1 A; sensor power 2 channels of +24 VDC at 2.2 A, also able to drive external 24 VDC horn/strobes
- Enclosure: weatherproof NEMA 4X fiberglass for outdoor and washdown areas; 11.3" H x 9.3" W x 7.0" D; 6.0 lb
- Temperature range: 0°F to +122°F (-18°C to +50°C)
- Certification: SGS listed to UL 61010-1 and CSA C22.2 No. 61010-1-12; 2-year warranty
Common questions
What sensors can I connect to the GG-2?
Any gas sensor with an industry-standard 4-20 mA output, including the CTI sensor line. CTI notes it is not for temperature monitoring.
Can it power horn/strobes?
Yes. CTI states the GG-2 power supply can also drive external 24 VDC horn/strobes.
Specifications are based on the CTI (Calibration Technologies) product page for GG-2 Control Panel. Confirm fit, ratings and application requirements before ordering.
Disclaimer: The image shown is a general representation of the product category and may not depict the exact part number offered. Actual product appearance, specifications, and configuration may vary.