Description
The CTI GG-VL2-CO2 is a vent line carbon dioxide (CO2) detector that continuously monitors refrigeration system relief valves, using carbon dioxide-selective infrared sensing with a 0-5% (0-50,000 ppm) range and 4-20 mA output. The kit is delivered calibrated with the transmitter, sensor, enclosure and mounting kit.
Key specifications
- Target gas and range: carbon dioxide (CO2), 0-5% (0-50,000 ppm)
- Detection principle: infrared (NDIR dual beam); diffusion; T90 under 30 seconds
- Output: linear 4-20 mA (max input impedance 700 ohms); input power +24 VDC, 60 mA
- Accuracy and repeatability: +/- 2% of full scale; zero drift under 0.1% FS/month; span drift under 2% FS/month
- Enclosure: NEMA 4X 316 stainless steel, gasketed, hinged lid with captive screw, for non-classified areas; 4.8" H x 4.72" W x 3.35" D; 4 lb with mounting kit
- Temperature range: -40°F to +140°F (-40°C to +60°C); humidity 0-95% non-condensing
- Typical sensor life 5 to 7 years; replacement sensor GG-VL2-CO2-RS
- SGS listed to UL 61010-1 and CSA C22.2 No. 61010-1-12; 2-year warranty including sensor element
Common questions
Where should the GG-VL2-CO2 be mounted?
CTI recommends mounting it 3 to 5 ft above the roof line on the relief discharge to atmosphere, with the supplied 1/2" pipe nipple welded or threaded to the discharge. It can be installed indoors as long as the 1/2" plug remains installed.
Can it detect slow leaks?
CTI states it can detect "weeping valves" to help prevent refrigerant loss over time, as well as high-pressure releases.
Specifications are based on the CTI (Calibration Technologies) 2025 product catalog. Confirm fit, ratings and application requirements before ordering.
Disclaimer: The image shown is a general representation of the product category and may not depict the exact part number offered. Actual product appearance, specifications, and configuration may vary.