Description
The CTI GG-VL2-NH3 is a vent line ammonia gas detector that continuously monitors refrigeration relief valve vent headers. It uses an ammonia-selective catalytic bead sensor with a 0-1% (10,000 ppm) range and a 4-20 mA output. A mounting kit is included.
Key specifications
- Target gas and range: ammonia (NH3), 0-1% (10,000 ppm)
- Sensor: catalytic bead; diffusion detection; T90 response under 30 seconds
- Output: 4-20 mA linear; input power +24 VDC
- Enclosure: NEMA 4X 316 stainless steel, 18 gauge, gasketed, hinged lid; 4.8" H x 4.72" W x 3.35" D
- Operating temperature: -40°F to +140°F; humidity 5-100% condensing
- Accuracy +/- 2%; zero drift under 0.1% FS/month; span drift under 1% FS/month
- Wiring: 3-conductor shielded cable (Belden 8772 or equal), up to 1,500 ft
- Certification: SGS listed to UL 61010-1 and CSA C22.2 No. 61010-1-12; 2-year warranty on sensing element and transmitter
Common questions
Where should the GG-VL2-NH3 be mounted?
CTI recommends mounting it 3 to 5 ft above the roof line on the relief discharge, with the supplied 1/2" pipe nipple welded or threaded into the discharge.
What replacement sensor does it use?
The GG-VL2-NH3 uses the GG-VL2-NH3-RS ammonia replacement sensor element.
Specifications are based on the CTI (Calibration Technologies) product page for GG-VL2 Vent Line gas detector. Confirm fit, ratings and application requirements before ordering.
Disclaimer: The image shown is a general representation of the product category and may not depict the exact part number offered. Actual product appearance, specifications, and configuration may vary.